CLI quickstart

This walks through a complete tune from the command line against BHTune's built-in FOPDT process simulator — no OPC DA connection, gateway, or real plant equipment required. It's the fastest way to see the whole tuning lifecycle (relay test → calculated PID constants → history) end to end.

Run a zero-configuration demo tune

bhtune simulate

simulate is a defaulted subset of the full tune command (see CLI reference for every flag tune accepts against a real loop) — it needs no flags at all to run a complete MRFT test against a synthetic Flow-type loop, using a fixed internal PV/MV tag pair instead of a real OPC DA tag. A run typically takes under a minute:

No PID constant tags configured for this run's driver/template; skipping write-back.
Tune completed successfully (run id 1).

("No PID constant tags configured" is expected and correct here — the simulator driver has no PID constant tags to write to at all, so write-back is always skipped for simulate regardless of --write-pid. See bhtune tune for writing PID constants back to a real controller.)

Every run is persisted to BHTune's SQLite database (see Installation) the moment it starts, not just on completion, so even an aborted or crashed run leaves a record.

Look at what it calculated

bhtune history show 1
Run #1 — Tag name: Sim.Loop1.PV
Notes: —
Driver: Simulator
Outcome: Completed
Started at: 2026-08-16T06:51:28.165183623+00:00
Completed at: 2026-08-16T06:52:18.574446068+00:00
Template: Yokogawa CentumVP (Builtin)
Process/controller: Flow / Pi
Relay amplitude: 10%
Cycles skip/count: 1 / 2
Initial PV / MV: 50 / 50
MV range: 0 - 100
PV range: 0 - 100
Direction: Reverse
Samples recorded: 64
Timing:
Basis: FixedStep
Requested interval: 800 ms
Observed sample gaps: 63
Mean / max sample gap: 800.000 / 800.000 ms
Missed poll opportunities: 0
Oscillation period: 46500.000 ms
Approx. samples / period: 58.125
Sampling adequacy: adequate
Poll latency:
PV reads: count=64 mean=0.010 ms max=0.050 ms
MV writes: none
MV verification: none
Sample persistence: count=64 mean=0.100 ms max=0.500 ms
Total tick work: count=64 mean=0.200 ms max=1.000 ms
Restore: confirmed
Calculated results:
LEVEL STATUS KP TI(min) TD(min) PROP INTEGRAL DERIV REASON
Aggressive Valid 0.5885 0.0971 0.0000 169.9304 5.8256 0.0000 -
Moderate Valid 0.3941 0.0971 0.0000 253.7703 5.8256 0.0000 -
Sluggish Valid 0.2949 0.0971 0.0000 339.1090 5.8256 0.0000 -

Three response levels are always evaluated (Aggressive/Moderate/Sluggish) — see MRFT concepts for what they mean and how to pick one. A usable row has STATUS set to Valid; if the measured amplitude, period, or a converted PID value is zero, non-finite, or otherwise unusable, the row is retained as Invalid with a diagnostic reason and no numeric values, and cannot be written back. PROP and INTEGRAL here are the Yokogawa CentumVP template's own units (Proportional Band % and Reset Time in minutes); a different template reports these in whatever units that DCS/PLC family expects — see DCS/PLC templates.

history show also prints timing diagnostics, including the requested and observed cadence, sampling adequacy (adequate, marginal, or not assessed), and successful latency summaries for PV reads, MV writes, MV verification, sample persistence, and total tick work. Sampling adequacy is advisory: marginal does not automatically reject a valid result, but it is a reason to inspect the trend before applying constants.

Every run's exact numbers depend on the simulator's process parameters (--sim-gain/--sim-tau/--sim-dead-time/--sim-noise/--sim-seed). The simulator advances its process and MRFT timestamps by the same configured poll step, so zero-noise runs with the same inputs are reproducible even when host scheduling differs. A fixed --sim-seed also reproduces the configured noise sequence within the same supported build.

List every run so far, and export one run's per-tick samples:

bhtune history list
bhtune export 1 --format csv > run-1-samples.csv

By default nothing is ever deleted automatically — BHTune retains every run forever until you opt in to a retention policy. Set --retention-days/BHTUNE_RETENTION_DAYS/retention_days to a positive whole number in bhtune.toml (see Configuration reference) to delete runs older than that many days automatically on every startup, or run bhtune history prune --older-than-days <N> to prune on demand without waiting for the next startup — add --dry-run to see how many runs would be deleted first.

Try different loop and controller types

simulate accepts the same --process-type/--controller-type/--relay-amp flags as tune:

bhtune simulate --process-type temperature-heat-exchange --controller-type pid --relay-amp 15

PID (as opposed to P/PI) is only offered for the two Temperature process types, matching the tag conventions the built-in templates were authored against.

Point it at a real loop

Once opcda-bridge-gateway is reachable from wherever BHTune runs, bhtune tune runs the same test against a real OPC DA tag instead of the simulator:

bhtune tune \
--driver opcda --server Matrikon.OPC.Simulation.1 --bridge-host gateway.plant.local:7600 \
--tagname FIC101 --template "Yokogawa CentumVP" \
--process-type flow --controller-type pi --relay-amp 5

This reads live tags (PV, MV, ranges, mode, direction), switches the loop to manual, strokes the relay, and restores the loop when the test ends — see Safety before running this against anything connected to a real process, especially unattended. Live MRFT timestamps use monotonic elapsed time anchored to UTC, so NTP/manual clock changes cannot distort the measured relay period; real host, gateway, and OPC latency remains visible. Keep the host and gateway responsive and use a poll interval comfortably shorter than the expected oscillation period. Afterward, bhtune history show <run-id> reports the requested and observed sampling cadence, measured oscillation period, approximate samples per period, sampling adequacy, and successful operation-latency summaries. A live sample gap at least twice the requested interval is reported as a missed-poll warning without aborting the run or blocking write-back. To also write the calculated PID constants back:

bhtune tune ... --write-pid moderate --yes

--yes is mandatory alongside --write-pid for any non-interactive write — see Safety.

Scripting and automation

--output json emits exactly one parseable JSON value on stdout on every path (success, timeout, abort, write-back failure), with meaningful, distinguished process exit codes, so a scheduler can tell a clean completion, a Ctrl+C abort, and a failed write-back apart without parsing prose — see Automation and the exit code table in AGENTS.md for the full contract.

Next steps

  • Web GUI quickstart — the same tuning engine, driven from a browser.
  • Safety — what happens on Ctrl+C, a stalled read, or a timeout, and how PID write-back is verified and rolled back.