bhtune-server is a single binary that serves both a REST + Server-Sent-Events API and the built React frontend — no separate Node process, reverse proxy, or Docker container required on the target host. This walks through running a complete tune from a browser, against the built-in simulator.

Build and run

pnpm install
pnpm --filter bhtune-frontend run build # embeds frontend/dist/ into the server binary
cargo run --release --bin bhtune-server
bhtune-server listening on http://127.0.0.1:8787

Open that URL in a browser. If you skip the frontend build, the server still starts and serves its API — every /api/* route works — but any other path returns a clear 503 the web UI has not been built yet instead of a blank page, naming the exact command to run.

The header's theme button switches between Catppuccin light and dark palettes. The selected palette is remembered by the browser.

The header also shows whether the BHTune HTTP service is reachable. Its status includes screen-reader text and a tooltip; a healthy server indicator does not test OPC DA connectivity.

For a visual tour of every Full and Demo page, see the Web UI visual reference.

Restricted Demo mode

A server configured for Demo mode exposes a simulator-only browser experience. The frontend loads the server capability document before it queries run history or renders mode-sensitive routes. That request lazily sets the host-only anonymous Demo cookie but does not create a database row; storage begins only when the browser starts its first accepted tune. Config, OPC browsing, notes, and PID write-back are absent; templates are limited to the built-in read-only catalog. Demo run history, detail, streaming, cancellation, export, and deletion use the same /api/runs paths as Full mode. Starting a tune sends only the normalized simulator fields shown by the Demo form, with a fixed safe tag, bounded simulator ranges and timing values, and a controller direction that must provide negative feedback for the selected positive or negative process gain. The Demo defaults are a 0–100 PV/MV range with initial values of 50, gain 1.0, time constant 0.5 seconds, dead time 1 second, zero noise, relay amplitude 10%, one skipped cycle, two counted cycles, and zero seconds of noise protection.

Demo policy limits and simulator timing are fixed application-owned values rather than public configuration controls; a deployment configuration may only declare the exact contract. Each run uses the stable Simulator demo identity. Demo history belongs to the anonymous browser session that created it. Another browser profile or private window cannot list or open those runs. The Demo form draft is stored only in that browser and expires 24 hours after its last edit. A usage-limit message advises waiting before retrying (429), while temporary service-capacity failures (503) advise retrying after a short pause. Full mode keeps the complete behavior described below.

bhtune-server has no command-line flags of its own (unlike bhtune, it doesn't use clap yet). Every setting — including which port it binds — is resolved from a config file or environment variable, the same way the CLI resolves its own flags:

BHTUNE_BIND=0.0.0.0:8080 cargo run --release --bin bhtune-server # bind elsewhere, e.g. for LAN access

Binding anywhere other than 127.0.0.1 exposes the server to your network with no authentication — see Safety before doing this outside a trusted, isolated OT network. Authentication is a planned, not yet shipped, feature (see the roadmap in the main README).

Frontend development mode

If you're changing the frontend itself, run the Vite dev server alongside a running bhtune-server instead of rebuilding on every change — Vite proxies /api/* requests through to the real server so both stay in sync:

cargo run --bin bhtune-server & # first, in one terminal
pnpm --filter bhtune-frontend run dev # then, in another -- hot-reloads on save

The Vite development server binds all local interfaces and allows the asus hostname, so a second host on the trusted local network can open http://asus:5173. Frontend edits are deployed through hot module reload after each save; restart bhtune-server after Rust or API changes. The proxy keeps browser API calls same-origin to the Vite page; Full mode accepts that development flow while continuing to reject cross-site browser mutations. The development server and API have no authentication, so do not expose them beyond a trusted network.

Run a tune

  1. Tune (/runs/new) — the app's default landing page, and the first item in the header nav. One form covering the per-tune settings for bhtune tune: connection (which driver — OPC DA or the simulator), tag mapping, test parameters (process type, controller type, relay amplitude, cycles), simulator parameters (gain/time constant/dead time/noise, when the simulator driver is selected), and automatic PID settings. Submitting POSTs to the same /api/runs endpoint the CLI's bhtune-server mode exposes — there's exactly one API, used by both the browser and any script that wants to drive a run over HTTP directly. Multiple tunes can run at the same time. PID writes and restores remain exclusive with active tunes because they modify live controller values directly. The Start tune and Cancel actions remain at the top of the page while you configure the tune.

    • Switching the driver to Simulator greys out every field the simulator genuinely ignores (OPC server ProgID, bridge host, tag name, automatic PID settings, and quality options) rather than hiding them, so the form doesn't reflow and the greyed field itself explains what the simulator doesn't use. The template stays enabled intentionally: the simulator ignores its DCS tag mappings, but its PID type and unit conventions still format calculated results (for example, Yokogawa uses proportional band while the other built-in templates use gain). PV/MV ranges, controller direction, and every engine parameter also stay enabled because the simulator needs them.

    • Test parameters show concrete Process defaults for cycles to skip, cycles to count, and noise protection based on the selected Process type. Changing Process type replaces all three values; Reset process defaults restores those values without resetting the rest of the form. These are process-type defaults rather than DCS/PLC template settings.

    • Switching to OPC DA reveals a Browse servers button next to the ProgID field. It opens an on-demand picker populated by the bridge gateway, listing every OPC DA server registered on it as clickable buttons — no need to already know (or spell correctly) a ProgID like Matrikon.OPC.Simulation. A Browse tags button next to the Tag name field (enabled once a ProgID is entered) opens a lazily-expanding tag tree fetched one level at a time from the gateway. Already-loaded levels are reused when you revisit an expanded branch. Hierarchical servers such as Yokogawa CSHIS can be expanded through nested controller/block levels until their PV leaves; dotted and slash-separated item IDs are supported. The first node is selected automatically when the tree loads, and the selection panel stays in place while browsing. The main form's collapsible Loop mapping section is the single place to inspect the complete tag set the active template derives from the selected PV and the direction/range inputs used for the tune. Each row shows its effective value and source. Tag mappings use Template tag or Custom tag; direction and range mappings use Template tag, Custom tag, or Fixed value. Switching to a custom tag starts with the template-derived value; fixed direction/range values must be entered explicitly. Each mapping row is a labeled group, and its source choices are exposed as an accessible pressed-button set. Use a row's Reset button or Reset all mapping overrides to return to template/live values. Simulator direction and ranges are kept separately from OPC fixed overrides. The browser itself stays focused on browsing and testing the selected PV tag. It offers a Read selected tag action showing a live value

      and its quality. Double-clicking a browsed leaf or indexed-search result selects it; double-clicking any expandable node, including a branch-and-item node, expands or collapses it. Selecting Select tag writes the selected tag with its final component replaced by the active template's process-variable suffix into the Tag name field. Changing templates likewise replaces the final component with the new template's process-variable suffix, regardless of what the previous component was, preserving the rest of the tag path.

      For example, browsing Area01.FIC101.OUT with a template whose process_variable_suffix is PV produces Area01.FIC101.PV: BHTune replaces the final component after the last ., !, or / rather than blindly appending .PV.

      Clicking Select tag performs a fresh read of the original selected item (before suffix replacement) and proceeds immediately only for Good OPC quality; Uncertain or Bad quality opens a warning with choices to select a different tag or proceed anyway. Proceeding only selects the item; tune execution still applies its live-reading quality safeguards. Changing the base Tag name — by editing it, selecting a browser tag, or switching templates — resets every Custom tag selector to Template tag and clears custom tag values, including custom direction/range read tags. Fixed value direction and range selections and values remain unchanged. The Config page controls whether Uncertain readings are accepted during tuning; they are accepted by default, while Bad quality is always rejected. Reopening the browser expands the available path to the current Tag name, selects that node, and scrolls it into view; an unavailable tag falls back to the root level. Indexed search is an optional whole-server accelerator. A fresh gateway has no enrolled servers and does not index every registered OPC DA server automatically. Use Build index in the tag browser to enroll the selected ProgID and start its first build; no gateway TOML edit or restart is required. After the first successful build, the gateway automatically refreshes the index according to its configurable seven-day policy. The browser also provides Refresh now, Retry build, Disable auto-refresh, Enable auto-refresh, and Delete index actions. Disabling automatic refresh keeps the existing index and searchable data; deleting it shows a temporary deleting state while the gateway removes the index and enrollment, then leaves ordinary browse, direct ItemID entry, live reads, and tuning available. If indexing is not enrolled or is still building, the global search field is disabled, but the lazy tag tree and other operations remain available. Completed non-fatal inventory diagnostics remain available through the gateway/API and diagnostic CLI; the browser shows a visible message for a failed index state. When automatic refresh is enabled, the next scheduled refresh appears as a relative days-and-hours countdown, with the exact scheduled time available on hover.

    • A Notes field records optional operator context, observations, or follow-up actions. Notes are included when the run starts and can be edited or cleared from the run detail page while the run is active or after it finishes.

    • Every field except Notes is autosaved to the server as the app-wide New tune draft, including OPC values that are temporarily inactive while Simulator is selected. The draft follows you across browsers and machines rather than living in localStorage. Notes are intentionally left blank after a reload so one run's operator context is not copied into another. On an installation without a saved draft, the form quietly falls back once to the newest run's settings or the built-in defaults; this normal first-use state does not display an error. Duplicate this run takes precedence over both sources, and Reset to defaults replaces the saved draft with the built-in defaults. Connection, Test parameters, Loop mapping, Simulator parameters, and Automatic PID settings are independently collapsible and open by default. Controls that do not apply to the selected driver stay visible but disabled with an explanation.

    • Installation-wide MRFT timing and safety values are managed on the Config page, not on this form: MRFT delay, poll interval, whole-run timeout, driver-operation timeout, and restore timeout. They are stored under [tuning] in bhtune.toml, apply to future tune preparations, and are frozen into each run when it starts. The three process-dependent defaults in Test parameters remain per-tune values.

  2. Run detail (/runs/:id) — while a run is in progress, a live PV/MV trend chart updates in real time over Server-Sent Events (GET /api/runs/:id/stream), with line-only PV/MV series alongside the current relay switch count and cycles remaining. The initial PV/MV snapshot appears as soon as the server records it, before the first MRFT sample, so the chart does not wait for a complete relay tick to become visible. Independent OPC DA startup values are collected in one batched read; a setpoint is read separately only when the original mode is Auto. Simulator sample timestamps advance by the configured fixed poll step, matching the FOPDT process time rather than host scheduler timing, so repeated simulator runs retain the same trend timing and PID calculations across machines. Live OPC DA timestamps instead use actual monotonic elapsed time projected onto the run's UTC start, making clock adjustments irrelevant without hiding real scheduling or driver delays. BHTune is not a hard-real-time controller, so the host and gateway still need to remain responsive. The trend ends with a terminal point at the original MV after the run restores the loop. Short runs keep their first point at the left edge by reserving 12 configured poll intervals of x-axis horizon; unused future space stays blank until the trend is long enough to fit normally. The initial-reading and restored-MV boundary markers are presentation-only and do not alter persisted samples or CSV/JSON exports. A Cancel button stops the run early (the same Ctrl+C-triggered abort-and-restore path the CLI uses — see Safety). Once calculated results exist, the same page promotes them directly below the heading and before the trend:

    • The Calculated results panel is the primary post-tune action area. Each Aggressive/Moderate/Sluggish row has a Review & write button that works independently of any --write-pid choice made before the run started. The safety review modal names the loop tag, response level, snapshotted parameter labels, exact destination tags, and exact values before anything is sent. It opens as a centered viewport popup. Confirming an Apply closes the popup immediately while BHTune writes and verifies the values in the background; successful writes stay silent, while transport failures or failed physical writes/readbacks appear in a page-level alert. The same popup component is used by the OPC server and tag browsers. When no results exist, the panel stays in its lower diagnostic position and explains that no results were calculated.

    • A mutable Notes field with Save notes and Clear notes actions. Notes are metadata, so editing them does not interrupt an active tune.

    • A PID change history table of every PID change this tune has made, each with a pre-write readback, a post-write readback, and a rollback status. The newest successful write shows a Restore previous values button that opens the same safety review modal and lists the recorded pre-write values before restoring them. Confirming a restore closes the popup immediately while BHTune works in the background; successful restores stay silent, while transport failures or failed physical restores/readbacks appear in a page-level alert.

      Both buttons are disabled — with the reason shown as text, never a silent, unexplained grey button — unless the run is finished, used the OPC DA driver, has PID constant tags configured, and recorded which OPC server/bridge host it connected to.

    • Export CSV/Export JSON download links and a Delete tune button (with a confirmation prompt — deleting a tune also removes its recorded measurements and results, and cannot be undone).

    • A Duplicate this run button, returning to the New tune form prefilled from this run's tune settings instead of the newest run's; Notes starts blank. It preserves the original Template tag, Custom tag, and Fixed value mapping sources, including template-derived direction and range values that were stored as null or omitted fields.

    • The Calculated results table uses the constant names and converted values from the run's snapshotted template. A Yokogawa run therefore shows P, I, and D instead of the engine's intermediate Kp, Ti, and Td columns. The derivative column remains visible for PI runs and shows 0, the explicit value used to clear stale derivative action. A result whose amplitude, period, or converted PID values are zero, non-finite, or otherwise unusable is shown as Invalid with a reason and no numeric values; its calculated-result write action is disabled.

    • The collapsed Sampling diagnostics section reports sampling adequacy: adequate means at least six observed samples per measured period, marginal means fewer than six, and not assessed means no usable finite period was available. This is an advisory signal, not an automatic block on a valid result. Detailed sample-gap and successful operation-latency diagnostics remain available through the CLI, API, and structured logs.

    • Run-detail sections are independently collapsible. Calculated results, Trend, Summary, Notes, Test configuration, Initial readings, and PID change history start expanded so the main result and PID audit information is immediately visible. Sampling diagnostics starts collapsed because it is advisory. Detailed MV command/readback evidence is available through bhtune history show, the run-detail API, and structured logs when deeper support or safety analysis is needed.

    Detailed polling timing diagnostics remain available through bhtune history show, the run-detail API, and structured logs, but are not part of the normal web run-detail view.

  3. History (/runs) — every past tune, shown by Tag name and filterable by outcome and process type, with the same detail view available for any completed run — not just the one you just started.

  4. Templates (/templates) — the four built-in DCS/PLC templates are listed on first launch (seeded automatically into the database). Open one to see its full tag-suffix mapping, or create a new one instead of hand-editing a TOML file.

Explore the API directly

Every route is documented at /api/docs (an interactive Scalar UI generated from the same OpenAPI 3.1 spec the frontend's TypeScript client is generated from — the two can never drift apart), and the raw spec is at /api/openapi.json. A minimal health check:

curl http://127.0.0.1:8787/api/health
# {"status":"ok","version":"<application-version>"}

The web GUI displays this application version beside its connection status in the header.

Starting a tune over HTTP directly (no browser) needs the same per-tune fields as the CLI's tune/simulate commands — see /api/docs for the full request schema, including the extra range/direction fields the simulator driver requires that a real OPC DA driver would instead read live from the DCS. The global [tuning] settings are read from the server's configuration when the run is prepared.

Next steps

  • CLI quickstart — the same tuning engine, scriptable for scheduled/ unattended runs.
  • Safety — cancellation, quality enforcement, and write-back rollback, all shared between the CLI and the server.
  • Configuration — TOML-backed global tuning, quality, and retention policies.
  • DCS/PLC templates — the tag-mapping system behind the Templates screen.