MRFT concepts

BHTune's tuning engine runs an MRFT (Modified Relay Feedback Test) against a loop instead of asking you to guess PID constants or step the process open-loop. This page explains what that means in practice — enough to interpret a run's results and choose sensible parameters, not a full control-theory derivation.

The relay feedback idea

Classic relay feedback (Åström & Hägglund) forces a process into a small, controlled oscillation by switching the manipulated variable (MV) between two fixed values instead of using a normal PID controller. Where the process crosses its setpoint, the relay flips; the resulting oscillation's period and amplitude are enough to estimate the process's ultimate gain and ultimate period — the same two numbers classic Ziegler-Nichols closed-loop tuning is built on — without ever pushing the process to the edge of instability the way a true Ziegler-Nichols closed-loop test does.

"Modified" refers to the specific relay-switching refinements BHTune's engine implements: hysteresis around the switch point (so measurement noise near the setpoint doesn't cause spurious extra switches), a configurable number of initial cycles to skip before any switches are counted (letting initial transients settle out), and noise-protection delays around each switch. These are exactly the same refinements the legacy tool implemented, ported unchanged.

What actually happens during a test

  1. BHTune reads the loop's current state — PV, MV, ranges, mode, and controller direction — and validates all of it (see Safety) before touching anything.
  2. The loop is switched to manual. Nothing is calculated yet; a test is a real, physical experiment on a real, running process.
  3. The MV is stepped by the relay amplitude (a percentage of the MV range you choose) every time the PV crosses the switch threshold, in the direction that opposes the process's own moves — this is what "closes the loop" around the relay instead of a PID block.
  4. Every PV sample is polled and logged (by default every 800 ms, matching the legacy tool's timer) using the global [tuning].poll_interval_ms setting, building up a picture of the resulting oscillation: its peaks, its troughs, and the exact times each switch happened. When an OPC DA relay command is awaiting confirmation, that same poll also requests the MV so BHTune can verify the physical command before the engine advances.
  5. The first few cycles are skipped (the visible Process defaults are selected per process type) before any switch is counted, and then a fixed number of cycles are counted to measure the steady-state oscillation. Noise-protection delays around relay switches are also shown as process defaults in the New tune form.
  6. On the final step, the MV snaps back to its starting value rather than taking one more full relay step — so the loop is left close to where it started, not mid-swing.
  7. The loop is restored to its original mode (and setpoint, if it was changed) — see Safety for exactly what "restored" guarantees.

For OPC DA runs, each accepted MV relay command is also read back and checked against its commanded target before another relay can replace it. This verification uses a fixed internal four-second confirmation window; a command that remains outside tolerance, or whose matching readback arrives after the deadline, aborts the test and starts restoration. Simulator and replay runs do not add this live-I/O verification step.

How boundary samples are measured

BHTune keeps two kinds of extrema while the relay test runs. The hysteresis extrema determine when the next relay switch is needed; the measurement extrema determine the PV amplitude used for the final tuning calculation. At a switch, the hysteresis extrema retain the established switching behavior, while the just-recorded switch sample seeds the new measurement interval. That shared boundary sample can therefore contribute to both adjacent half-cycles.

This distinction matters when polling is sparse. If the new half-cycle has no later sample on its own side of the initial PV, resetting its measurement extrema to the initial value would make a real oscillation look flat and could produce an unusable zero amplitude. Seeding the measurement interval with the switch sample prevents that measurement artifact without changing hysteresis, switch timing, MV commands, or actuation verification.

The other operational timing and safety limits are installation-wide settings under [tuning]: MRFT delay padding, the whole-run timeout, driver-operation timeout, and restore timeout. They are configured on the web GUI's Config page or in bhtune.toml, apply to future tune starts, and are frozen into each run when preparation begins. OPC DA requires a restore timeout of at least four seconds because MV actuation confirmation can take up to that long. History also records successful PV-read, MV-write, MV-verification-read, sample-persistence, and total-tick-work latency summaries. A pending relay's batched PV/MV request may appear in both the PV-read and MV-verification categories; these are overlapping descriptions of one OPC operation, not durations to sum. The measurements help distinguish a slow driver or database from an overly aggressive polling request; failed, cancelled, and timed-out operations are not treated as successful latency samples.

The MV values shown in the trend, persisted samples, and sample exports are the commanded values produced by the MRFT engine. The actual MV values returned by OPC DA readbacks are separate actuation-audit records available through run history, the API, and structured logs; keeping these series separate preserves the engine's timing and export semantics while making physical actuation evidence available.

Nothing here writes a PID constant. That only happens if you explicitly ask for it (--write-pid <level> on the CLI, or the Automatic PID settings section of the New tune form) — see PID write-back.

From oscillation to PID constants

Once the counted cycles are captured, BHTune measures the oscillation's average period and amplitude, and combines them with the relay amplitude to estimate the process's ultimate gain and period. Three sets of PID constants are then calculated from that estimate — Aggressive, Moderate, and Sluggish — using per-process-type tuning-constant matrices (the same approach, and the same underlying constants, as the legacy tool). Which one to actually use depends on how much overshoot/oscillation the process can tolerate:

  • Aggressive — fastest disturbance rejection, least tolerant of model error; best for well-behaved, fast loops (flow, pressure) where a little overshoot is harmless.
  • Moderate — a reasonable default for most loops.
  • Sluggish — slowest, most conservative; best where overshoot is expensive or dangerous (level loops feeding a downstream process, some temperature loops).

bhtune history show <run-id> (or the run detail screen in the web GUI) always reports all three, in the units your DCS/PLC template expects (Proportional Band % or Gain, Reset Time or Reset Rate, Derivative Time or Derivative Gain — see DCS/PLC templates), so the choice is made after seeing the numbers, not before.

Every response-level result is checked before it is stored as usable tuning data. A non-positive or non-finite amplitude or period, or a non-finite intermediate or converted PID value, is stored as Invalid with a diagnostic reason and no numeric values. The CLI and web GUI do not offer that invalid row as a calculated-result write target. A run also reports whether its measured sampling was adequate, marginal, or not assessed in the collapsed Sampling diagnostics section on the web run-detail page; a marginal advisory is a reason to inspect the trend and timing diagnostics, not an automatic rejection.

The web run-detail Calculated results table uses the constant names from the run's snapshotted template, so a Yokogawa run shows P, I, and D rather than generic engine labels. It keeps the derivative column for PI runs and displays 0, because the write path explicitly clears stale derivative action for controllers without a derivative term. When results exist, the web GUI promotes this panel above the trend. Each response level has a Review & write action that shows the exact destination tags and values in a safety review popup before writing. The popup is centered over the viewport and shared with the OPC server and tag browsers. Confirming an Apply closes the popup immediately; successful writes stay silent, while transport failures or failed physical writes/readbacks appear in a page-level alert. The newest successful write can be restored from the same popup using its recorded pre-write values. Confirming a restore closes the popup immediately as well; successful restores stay silent, while transport failures or failed physical restores/readbacks appear in a page-level alert. The run-detail sections are independently collapsible. Calculated results, Trend, Summary, Notes, Test configuration, Initial readings, and PID change history start expanded, while Sampling diagnostics starts collapsed so the primary results and PID actions remain prominent. Detailed MV command/readback evidence is available through bhtune history show, the run-detail API, and structured logs rather than the normal web run-detail page.

Controller type and process type

  • P and PI are offered for every process type; PID is only offered for the two Temperature process types, matching the tag conventions the built-in templates were authored against (a temperature loop's derivative term is usually meaningful; a flow loop's usually isn't, and adding one to a fast, noisy loop tends to do more harm than good).
  • Process type (flow, pressure — line or vessel, level, temperature — mixing or heat exchange) drives the default cycles-skip/cycles-count/noise-protection values and which row of the tuning-constant matrices is used. These defaults come from the same lookup tables the legacy tool used. The web form displays the selected process type's values in its Process defaults subgroup and provides a reset action; changing process type also restores its values. They are not DCS/PLC template properties: templates define tag conventions and PID units. Override the process defaults explicitly if your process needs something different. CLI and HTTP callers may omit them to use the server-side defaults.

Next steps

  • Safety — what BHTune does (and refuses to do) around a live, running process, including cancellation, quality enforcement, and write-back rollback.
  • DCS/PLC templates — how a template's suffixes and units turn a bare tag name into the full set of reads/writes a tune needs.
  • CLI quickstart / Web GUI quickstart — run a test yourself against the built-in simulator.